Central gas detection unit for the connection up to 3 UR..13.type Detectors; with
optical LED interface (voltage, fault, gas alarm) and acoustics via internal buzzer.
In self-extinguishing plastic case, for wall or front panel mounting:
– 230 Vac power supply
– Optional battery charger (with UZY13-CB module)
– Control outputs for gas alarm and failure:
n.1 control for 12 Vdc E/valves (NO / NC)
n.1 Open Collector 12 Vdc 300 mA max for external buzzer
n.1 SPDT relay 250Vac 5A (with optional module UZY20-R)
– Degree of protection: IP54
UCE13.5 Central Unit for 3 threshold probes
Gas detection threshold probes for power plants
– Power supply: from UCE.. Central Unit
– Degree of protection IP44
URG13/A Methane gas detection probe
URG13P/A LPG detection probe GPL
URO13/A CO carbon monoxide detection probe
– Power supply: from UCE.. Central Unit
– Degree of protection IP54
URG13.S Methane gas detection probe
URG13P.S LPG detection probe
URO13.S CO carbon monoxide detection probe
– Power supply: from UCE.. Central Unit
– Degree of protection IP44
URG13 Methane gas detection probe
URP13 LPG detection probe
URO13 CO carbon monoxide detection probe
Accessori per UCE13.5 ed EXT6.5
Extension Unit of the UCE13.5 Control Unit, for the connection up to 6 UR..13 type probes, for each UCE13.5 input.
Optical LED interface (voltage presence, fault, gas alarm) and acoustic interface via internal buzzer.
In self-extinguishing plastic case, for wall or front panel mounting:
– 230 Vac power supply
– Optional battery charger (with UZY13-CB module)
– SPDT 250Vac 8A relay (with optional module UZY20-R)
– Degree of protection: IP54
Auxiliary relay card for UCE13.5 and EXT6.5
Positive logic operation (normally excited).
It de-energizes in the event of an alarm.
Potential-free changeover contact: 250VAC 5 (3) A